Résumé : In the early 1980s, relaying engineers conceived a technology allowing a huge step forward in the monitoring of power system behavior: the synchrophasor, i.e. the estimation of a phasor representation - amplitude and phase - of a sinusoidal waveform at a given point in time thanks to highly accurate time synchronization of a digital relay. By measuring synchrophasors across the power system several times per second, and centralizing the appropriate information in a hierarchical way through a telecommunication network link, it is now possible to continuously monitor the state of very large systems at a high refresh rate.

At the beginning, the phase angle information of synchrophasors was used to support or improve the performance of classic monitoring applications, such as state estimation and post-mortem analysis. Later, synchrophasors were found to be valuable for the detection and analysis of phenomena that were not monitored previously, such as system islanding and angular stability. This allows a better understanding of system behavior and the design of remedial actions in cases where system security appears to be endangered. Early detection and even prediction of instabilities, as well as validation and improvement of the dynamic models used for studies, have thus become possible.

However, a power system is rarely stationary and the assumptions behind the definition of “phasor” are not completely fulfilled because the waveforms' frequency and amplitude are not constant over a signal cycle at fundamental frequency. Therefore, accuracy of synchrophasor measurements during dynamic events is an important performance criterion. Furthermore, when discontinuities (phase jumps and high magnitude variations) and harmonics disturb the measured analog signals as a consequence of switching actions or external disturbances, measurements provided to the “user” (the operator or the algorithms that will take decisions such as triggering alarms and remedial actions) require a certain robustness.

The efforts underpinning this thesis have lead to the development of a method that ensures the robustness of the measurement. This scheme is described and tested in various conditions. In order to achieve a closer alignment between required and actual measurement performance, it is recommended to add an online indicator of phasor accuracy to the phasor data.

Fast automated corrective actions and closed-loop control schemes relying on synchrophasors are increasingly deployed in power systems. The delay introduced in the measurement and the telecommunication can have a negative impact on the efficiency of these schemes. Therefore, measurement latency is also a major performance indicator of the synchrophasor measurement.

This thesis illustrates the full measurement chain, from the measurement of analog voltages and currents in the power system to the use of these measurements for various purposes, with an emphasis on real-time applications: visualization, triggering of alarms in the control room or remedial actions, and integration in closed-loop controls. It highlights the various elements along this chain, which influence the availability, accuracy and delay of the data.

The main focus is on the algorithm to estimate synchrophasors and on the tradeoff between accuracy and latency that arises in applications for which measurements are taken during dynamic events and the data must be processed within a very limited timeframe.

If both fast phasors and slower, more accurate phasors are made available, the user would be able to select the set of phasors that are the most suitable for each application, by giving priority to either accuracy or a short delay.

This thesis also tentatively identifies gaps between requirements and typical measurements in order to identify current barriers and challenges to the use of wide area measurement systems.

A specific application, the continuous monitoring of oscillatory stability, was selected in order to illustrate the benefits of synchrophasors for the monitoring, analysis and control of power system behavior. This application requires a good phasor accuracy but can allow for some measurement delay, unless phasor data are used in an oscillation damping controller. In addition, it also relies on modal estimators, i.e. techniques for the online identification of the characteristics of oscillatory modes from measurements. This field of ongoing research is also introduced in this thesis.